| Evaluation
,Features |
Value
Ranges |
|
| DC
Process |
| High
Accuracy |
0,01
% |
| Input
Ranges programmable |
0/4-20
mA, 10-50 mA, 0/2 - 10V,
0/1-5 V, +- 100 mV, +- V, +- 10 V |
| Non-Linear
Scaling up to 10 points |
-19999....99999 |
| Process
Offset value |
-19999....99999 |
| Elapsed
time of Alarm 1(seconds) |
0
sec .... 999.9 min |
| Totalising
of process values by interval |
seconds,
minutes, hours |
| option:
tare function-> process offset |
-199999....99999 |
|
| Temperature |
| High
Accuracy |
0,1
% |
| Input
Ranges programmable |
J,T,K,N,B,R,S,PT
100 |
| Sensor
break detection |
2
seconds max |
| Input
Range can be trimmed |
Range
min to Range max |
| Elapsed
time of alarm 1 (Seconds) |
0
sec.... 999.9 min |
|
| DC
Volt/Amps |
| High
accuracy |
0,1% |
| DC
Volt range |
100
mV...600V |
| DC
Amps range |
1
mA...1 A, 2 A with shunt |
| Process
Offset |
-19999...99999 |
| Elapsed
time of Alarm 1 (Seconds) |
0
sec...999.9 min |
|
| Ac
Volt/Amps (RMS) |
| Ac
Volt range |
1
V...600V |
| Ac
Amps range |
1
mA ... 1A |
| Process
Offset |
-19999...99999 |
| Elapsed
time of Alarm 1 (Seconds) |
0
sec. ...999.9 min |
|
| Strain
Gauge |
| Input
Range |
0...100
mV |
| Auxiliary
Power Voltage programmable |
5
V, 10 V |
| Non-Linear
Scaling up to 10 points |
-19999...99999 |
| Process
Offset |
-19999...99999 |
| Elapsed
time of Alarm 1 (Seconds) |
0
sec. ...999.9 min |
| Totalising
of Process Values by interval |
seconds,
minutes, hours |
| Option:
Tare fuction -> Process Offset |
-19999...99999 |
|
| Remote
Display |
| Process
value via serial interface |
via
RS 485 (ASCII) |
| Alarm
1 and 2 monitored autonomously |
-19999...99999 |
| Min/Max
stored automatically |
-19999...99999 |
|
| Terminals |
|
| Signal
Inputs |
| General |
Common
mode rejection > 120 db at 50/60 Hz;
Line voltage rejection > 140 db
Series mode rejection up to 500 % of span
Temperature coefficient:+ 25 ppm / 0 C |
| Calibration |
according
to NS 4937, NBS 125 and IEC 584 (all units are factory calibrated)
, units can be calibrated by customer; uncalibrated measuring is indicated |
|
| Outputs |
| OUT
1 NPN |
Open
Collector; max 30V DC; max 100 mA |
| OUT
2 NPN |
response
time < 75 us |
| Relay
1, |
Changeover
(Form C); 240 V AC/3 A or 110 V AC / 5 A; pull-in |
| Relays
2 (opt.) |
time
8 ms |
| Auxiliary
Power |
24
V Dc, 30 mA max
for strain gauge: 5 V DC or 10 V DC, 60 mA max |
|
Option
: Control Input
(not with Option RS 485) |
| NPN |
High
> 3.0 V or open, Low < 2.0 V; 4.7 k0hm to V+
response time 25 ms |
|
| Special
Features |
- Programmable
display colour for normal and alarm operation
- Alarm programmable
as high or low; can be deactivated or blocked
- Output signals
programmable; can be inverted and/or stored
- Process offset
- Display filter
programmable up to 100 sec.
- Tare function
and non-linear scaling with 0735 A2 and 0735 A6
- Optional
Linear Output
- Optional
Communication interface RS 485
|
|
| Orderung
Data |
|