The ACS 140 covers the same power range from 0.37 to 2.2 kW, but the voltage range is wider,from 200 up to 480 V.The ACS 400 covers the power range from 2.2 to 37 kW for voltage ranges 380 to 480 V .
|
| Features |
|
| Technical Data |
| Mains connection | Power
range: 0.37 - 2.2 kW (ACS 140)/2.2kW-37 kW(ACS 400) Voltage :1-phase and 3-phase, 200-240 V +_ 10%,3-phase,380-480 V+- 10%. Frequency:50 or 60 Hz. |
| Motor Connection | Voltage:3-phase,
from 0 to UMAINS:UMAX
at field-weakening point. Frequency 0-250 Hz. |
| Standard control connections |
|
| Protection | Overcurrent,l2t protection, overvoltage, undervoltage, overtemperature, earth fault, output short circuit, input phase loss(3 phase unit only),power-loss ride through, motor overload, motor stall protection, loss of serial communication, loss of AI signal. |
| Environmental limits | Ambient temperature:0-400c, up to 500C with derating |
| Enclosure | Degree of protection: IP 20(IP21 or IP54-ACS 400) |
| Accessories |
|
| Easy Usage |
|
|
|